Laboratory also has facilities for undertaking tests on filter reactors and series damping reactors associated with LV capacitors. The laboratory with the unique facilities is the first of its kind in this part of the world. Recently, facilities for testing LV APFC panels have been augmented including temperature rise test.
RESOURCES:
- (a) Parallel Resonance Transformer of Rating: 50/40/30/20 kV ac, 6.8 MVA.
- (b) Parallel Resonance Transformer rating: 70kV/38/16.5/7.1kVac, 1750KVA.
- (c) HVDC Source of rating: 150 kV 500 mA.
- (d) Discharge current test setup for Series Capacitors
- (e) 3 Phase Transformer of rating: 975 KVA, 2.5kV ac.
- (f) 3 Phase Transformer of rating: 610 KVA, 2640/1760/880V ac
- (g) High Accuracy Capacitance/tan delta bridge system: Accuracy:3.5x10E-5.
- (h) Standard Capacitor: 1000 pF, 25 kV.
- (i) Precision Current Comparator up to 5000A.
- (j) Hot Air Oven: 1.8m x 1.8m x 2.0m (W x D x H), Amb to 150°C, Accuracy: 1°C.
- (k) Climatic test Chamber: Size: 2.00m x 2.20m x 2.50m (WxDxH),
- Temperature: - 70°C to 100°C ± 1°C, Humidity: 10% to 95% ± 2% RH.
- (l) Impulse generator of rating: 500 kV 15 KJ for HV capacitors
- (m) Impulse generator of rating 18kV,100 Joules for LV Capacitors,
- (n) 500 MHz Storage oscilloscope,
- (o) Harmonics Generator and filter.
- (p) 35kV DC, 1.1Amp HVDC Power Supply
MAJOR TESTS :
- Output test / Capacitance & tan delta test
- High Voltage Tests
- Short Circuit discharge test
- Test for discharge device
- Thermal stability test
- Sealing test
- Impulse voltage withstand test
- Self healing test on MPP capacitors
- Charge discharge test on LV capacitors
- Destruction test on LV capacitors
- Discharge current test for Series capacitors
- Disconnecting test on Internal fuses
- Electrical Endurance test for HV capacitors - Over voltage cycle test & Ageing test
- Endurance test on LV capacitors -Ageing test, Charge discharge cycle test & destruction test
TESTING OF LV APFC PANELS
Tests on LV APFC panels are carried out as per IEC 61921, IEC 60439 and IS 16636. The temperature rise test will be carried out on APFC panels with all capacitor units, detuned/damping reactors, if any, and other components connected. Temperature rise test can also be carried at elevated ambient temperature of 55°C.
ENVIRONMENTAL TESTS :
- Environmental tests are carried out on various switchgear and control gear as per IEC 62271-100,
- Environmental tests on various equipment: Electrical, Mechanical, Automobile, Medical, ATMs, etc. as per various customer protocols.
TEMPERATURE RISE TESTS :
- Temperature rise test on Line Traps up to 4000 Amps
- Temperature rise test and other relevant tests on detuned and harmonic reactors
TYPE & RANGE OF CAPACITOR TESTING :
Capacitor | Maximum Rating | Standard |
---|---|---|
HV Shunt capacitors (For Routine and Type tests) |
3500 kvar, 16 kV, 50 µF | IS 13925 Part 1 –2012, IEC 60871-1 – 2014, IEC 60871-4 – 2014, IEEE Std. 18 – 2012 |
HV Shunt capacitors (For Endurance test) |
1000 kvar, 20 kV , 8µF 1000 kvar, 9 kV, 50 µF |
IS 13925 Part 2 2002 IEC 60871-2 – 2014 |
HV Series capacitors (For Routine and Type tests) |
3500 kvar, 20 kV, 50 µF | IEC 60143 – 1: 2015 IEC 60143 – 3: 2015 |
HV Series capacitors (For Cold duty test) |
1000 kvar, 16 kV, 12µF | IEC 60143 – 1: 2015 IEC 60143 – 3: 2015 |
HV Capacitors for surge Protection. | 0.33 µF, 40 kV | IS 11548 – 1986 (Reaffirmed Mar 2006) |
LV Motor capacitors | 100 x 10 µF, 440 V ac | IS 2993 – 1998. IEC 60252 -1-2001 |
LV fan motor Capacitors | 100 x 10 µF, 440 V ac | IS 1709 – 1984 (Reaffirmed Mar 2006 Amendment No. 2) |
LV Capacitors for Lighting | 100 x 10 µF, 440 V ac | IS 1569 – 1976 (Reaffirmed 2001) IEC 61048: 2015, IEC 61049: 1991. |
LV Power capacitors of self-healing type. | 150 kvar, 1000 V ac | IS 13340 Part 1:2012, IS 13340 Part 2:2012 IEC 60831-1-2014 IEC 60831-2-2014 |
LV Shunt capacitors of non self – healing type. | 150 kvar, 1000 V ac | IS 13585 Part 1:2012 IS 13585 Part 2:2013 IEC 60931-1:1996 IEC 60931-2:1995 IEC 60931-3:1996 |
LV APFC Panels | 800 kvar, 440 V | IEC 61921-2017 IEC 61439-2011 IS 16636:2017 |
Capacitors for Power Electronics | IEC 61071- 2017 | |
Capacitors for Railway applications – Rolling Stock equipment | IEC 61881- 2010 |
Dr. T. Bhavani Shanker
Joint Director/HoD
Capacitors Division
Phone: +91 (0) 80 - 2207 2321
Mobile: +91 9448141980
E-Mail : tbs@cpri.in